Digital indicators and controlers
|
|
|
|
|
|
|
Programmable digital panel meter RPP401 |
Product description:
|
RPP401 is a microprocessor, LED output meter. It can cooperate with both pressure and LVDT
transducers. It has one standard voltage (0-10)V or current (0/4-20)mA input
and is equipped with two relay-outputs which make possible to control outer devices.
RPP401 is equipped with a stabilized power supply 24V to supply a transducer this meter
is cooperate with, in two or three wires system.
Four digit indicator can be scaled in any units. The choice of kind and range
of input signal, setting of indicator-range and histeresis of relay-outputs is made by four ,
keys and depends only on customer. Power supply for RPP401 is 230V/50Hz.
Display digit height is 14mm. RPP401 is placed in standard-made board-mounted casing,
in size of 48x96x133mm
|
|
Technical parameters: |
Power supply | 230V (+/- 10%) /50Hz |
Power supply inbuilt | 24 V/50 mA to supply transducers |
Current input signal | any within range 0÷20mA |
Voltage input signal | any within range 0÷10V |
Display | 4 digit, LED, red, height 14 mm |
Basic error | ≤ 0,1 % MR ±1 digit |
Outputs | two, relay, altered |
|
|
|
|
|
|
|
|
|
|
Wall-mounted controler RPN401 |
Product description:
|
RPN401 is a version of RPP401 but with a airtight wall-mounted casing in size 140x80x70mm.
Indicator's digit's height 20mm, makes possible remote readout. Optional handle makes possible
to fix meter on standard line 35 mm. Other parameters like in RPP401. |
|
Technical parmeters: |
Power supply | 230V /50 Hz, 4 VA |
Power supply inbuilt | 24 V/50 mA to supply transducer |
Current input signal | any within range 0÷20mA |
Voltage input signal | any within range 0÷10V |
Dispaly | 4 digit, LED, red, height 20 mm |
Basic error | ≤ 0,1 % MR ±1 digit |
Outputs | two, relay, altered |
|
|
|
|
|
|
|
|
|
|
Panel digital indicator PWC |
Product description:
|
PWC meters is a group of unprogramable panel meters with LED display.
This series can cooperate with both pressure and LVDT transducers. It is equipped with standard
voltage and current inputs and can be factory scaled in any units.
3,5 digit and 4,5 digit kinds are provided and also such ones with 24Vdc or 230V/50Hz power supply
All kinds of this group have standard panel casings with window in size 48x96 mm. |
|
Technical parameters: |
Power supply | ▪ 230 V/50 Hz, 4 VA
▪ 24V DC/300 mA
|
Current input signal | ▪ 0÷20 mA
▪ 4÷20 mA
|
Voltage input signal | ▪ 0÷10 V
▪ 0÷5 V
|
Display | 4 digit, LED, red, height. 13 mm |
Number of display digits | ▪ 3,5 digit (max. dispaly 1999) - PWC300
▪ 4,5 digit (max. dispaly 19999) - PWC400
|
Basic error | ▪ ≤ 0,3 % MR ±1 digit for series PWC300
▪ ≤ 0,1 % MR ±1 digit for series PWC400
|
Outputs | ARK rail mounted on casing's back |
|
|
|
|
|
|
|
|
|
|
Current loop meter PML1224 |
Product description:
|
PML meter is a device to measure current-flow in a two wire current loop 4-20mA.
This meter doesn't require any external supply, energy is taken directly from a current loop.
Voltage drop in the current loop doesn't exceed 3,6V when current 20mA flows.
Measurement is to see on 4 digits LED display in mA or in pressure, flow or temperature units.
Every setting is possible to change after having connected PML to a computer's port RS232
using configure program. It is possible to program linear or nonlinear characteristic.
This type of meter has miniature panel casing in size 24x48x82mm
The meter's digit's height is 10 mm. When using PML1224 it is easy to make readout in these places
of current loop where is difficult access to power supplies. |
|
|
|
|
|
|
|
|
|
|
|
Current loop meter ML1-P |
Product description:
|
ML1-P meter is a device to measure current-flow in a two wire current loop 4-20mA.
This meter doesn't require external power supply, it is powered directly from a current loop.
Voltage drop in the current loop doesn't exceed 5,5V when current 20mA flows.
Measurement is to see on 4 digits LED display in mA or in pressure, flow or temperature units.
Display range -1999 to 9999. The device has one additional isolated control output
"open collector". Every setting is possible to change by customer.
Line casing 35mm line monuted. ML1-P enables easy adding a local readout
of current loop in difficult access places. |
|
Technical parameters: |
Power supply | from loop 4÷20 mA |
Input | 4÷20 mA |
Voltage drop across input | 5,3 V |
Display | 4 digit LCD 8 mm |
Readout | any, customer programmable |
Display range | any within range - 9999 ÷ 9999 |
Alarm level | open collector (OC) easy programmable |
Basic error | 0,1% MR ±1 last digit |
|
|
|
|
|
|
|
|
|
|
Plug-in indicators WWC1000 |
Product description:
|
WWC1000 is a plug in indicator with a micropocessor display with LED readout. It cooperates with any
measure equipment with two-wire current 4-20ma output and standard electrical connection DIN43650.
WWC1000 enables adding local readout of measured quantity directly with transducer by putting in it between
connector and transducer. The range of four digit display LED may be free programmable (using keys under
enclosure) within range -1999 to 9999 and coma set anywhere. WWC1000 is supplied with measured signal 4-20mA
(voltage drop across input 5V) and doesn't require external power. Casing made with plastic in size 42,5x51,5x48,5mm. |
|
|
|
|
|
|
|
|
|
|
|
RSP-01 |
Product description:
|
RSP-01 is dedicated to measure and record linear displacement within span 1÷3000 mm and force
within range 50N÷100kN. There is an optional software which makes possible showing on
a computer shield diagrams of force related to displacement, displacement related to time,
and force related to displacement.
|
|
Technical parameters |
Power supply | 230V/50Hz |
Output signal | USB/RS232 MODBUS-RTU/ASCII |
Measure range | ▪ force 50N÷100kN
▪ displacement 1÷3000 mm
|
Accuracy | 0,25% MR |
Electrical connection | Amphenol-Tuchel |
Enclosure protection | IP54 |
Working temperature | 0÷50°C |
|
|
|
|
|
|
|
|
|
|
MPLC702 meter |
Product description
|
MPLC702 meter is dedicated to measure linear displacement within 1÷3000 mm
and pressure from 1,25 mbar to 1000 bar. Readouts of both measurements are
displayed on two indicators and let out as two voltage signals 0÷10V.
The meter works with any displacement transducer AC/AC class made by Peltron and also with any
pressure transducers with three wire output signal 0÷10VDC.
MPLC702 consists of LVDT module, power supply stage and two indicators. LVDT module consists of
generator and demodulator of wave 5 or 1 kHz. Power stage provide voltages which enable the entire meter
to work and also feeds the pressure transdudcer. Indicators show measured values in displacement
and pressure units. The power supply socket is embedded to the rear side of the meter and sockets for both
transducers and output signals are on the rear side too.
|
|
Technical parameters |
Power supply | 230V/50Hz |
Output signals | ▪ 0÷10 V
▪ 0÷10 V
|
Measure ranges | ▪ pressure to 1000 bar
▪ displacement 1÷3000 mm
|
Enclosure protection | IP54 |
Working temperature | 0÷40°C |
|
|
|
|
|
|
|
|
|